Notifications
You must be signed in to change notification settings - Fork 0
Validation Rules
SCD Visualizer runs 26 structural checks plus XSD schema validation on every loaded file.
Issues are classified by severity:
- Error — violates a hard rule; must be fixed
- Warning — potential problem; review recommended
Site-specific rules for Landsnet substation projects.
| Code | Severity | Description |
|---|---|---|
LNET_001 |
Error | Duplicate IED name |
LNET_002 |
Error | Duplicate ConnectedAP IP address |
LNET_003 |
Warning | IED description missing or empty |
LNET_004 |
Warning | IED manufacturer missing or empty |
LNET_005 |
Warning | IED type missing or empty |
LNET_006 |
Warning | IED configVersion missing or empty |
LNET_007 |
Error | GSEControl missing address element |
LNET_008 |
Error | SampledValueControl missing address element |
LNET_009 |
Error | Duplicate GSE/SMV MAC address |
LNET_010 |
Error | GSEControl VLAN-PRIORITY below minimum (configurable) |
LNET_011 |
Error | SampledValueControl VLAN-PRIORITY below minimum |
LNET_012 |
Error | GSEControl MinTime below minimum (configurable) |
LNET_013 |
Error | GSEControl MaxTime above maximum (configurable) |
LNET_014 |
Warning | IED has no GSEControl (no GOOSE publishing) |
LNET_015 |
Error | Duplicate GSE/SMV APPID |
LNET_016 |
Error | ConnectedAP IP address is not a valid IPv4 address |
LNET_017 |
Error | ConnectedAP subnet mask is not valid |
LNET_018 |
Warning | IED has no SampledValueControl (no SV publishing) |
Thresholds for LNET_010–013 are read from validation_config.json.
Standard structural rules applicable to any IEC 61850 SCD file.
| Code | Severity | Description |
|---|---|---|
IEC_001 |
Warning | GOOSE subscription (ExtRef) not resolved to a known publisher dataset |
IEC_002 |
Warning | SV subscription (ExtRef) not resolved to a known publisher dataset |
IEC_003 |
Error | ExtRef element missing required binding attributes (ldInst, lnClass, doName) |
IEC_004 |
Warning | IED name does not match expected naming convention |
IEC_005 |
Warning | IED not referenced in any Substation hierarchy (no LNode link) |
IEC_006 |
Warning | LN lnType reference has no matching DataTypeTemplates entry |
IEC_007 |
Warning | GSEControl or SampledValueControl dataset contains no FCDA entries |
IEC_008 |
Error | confRev attribute is zero or missing on a control block |
The full IEC 61850-6 XML schema is validated using xmllint-wasm. The SCL edition is auto-detected:
Header version/revision
|
Schema used |
|---|---|
2007 / B
|
Edition 2 (2007B) |
2007 / B4
|
Edition 2.1 (2007B4) |
Schema issues are reported as SCL_XSD_001_<line> with the exact xmllint error message.
In the Issues view, individual check codes can be waived. A waived check is excluded from the issue count in the top bar and from the health gauge. Waived codes are stored in localStorage per browser session.
To waive a check: click the waive button on any issue row in the Issues List view.
Edit validation_config.json at the project root to adjust LNET_010–013 thresholds:
{
"goose": {
"vlan_priority_min": 4,
"min_time_ms": 2,
"max_time_ms": 1000
},
"sv": {
"vlan_priority_min": 4
}
}